CW-5200TG Industrial Water Chiller
To maximize the lifespan of your laser tube, ensure the chiller is powered on 5 minutes before laser operation. Periodically check the water level via the rear gauge to prevent dry-running the pump.
製品紹介
The CW-5200TG Industrial Chiller is meticulously engineered for the reliable and powerful cooling of laser systems and industrial machinery. Featuring an intelligent temperature control system, this unit automatically adjusts water temperature based on ambient conditions, ensuring optimal performance in demanding environments. Its compact design is complemented by sturdy handles for portability, while the durable steel construction ensures long-lasting service in heavy industrial settings.
製品仕様
| Parameter | Specification |
|---|---|
| モデル | CW-5200TG (AG/AH) |
| Working Voltage | AC 1P 220-240V / 110V (50/60Hz) |
| Total Rated Power | 0.68 KW |
| 冷却能力 | 1.75 KW (5970 Btu/h) |
| 温度安定性 | ±0.3℃ |
| Pump Flow Rate | 13 – 16 L/min |
| Max. Lift | 12M – 16M |
| タンク容量 | 6 L |
| 冷媒 | R410a / R407C |
| Machine Dimensions | 560 × 285 × 470 mm |
製品の特徴

Intelligent Temperature Control
Equipped with two control modes (Constant & Intelligent), the CW-5200TG allows users to set a fixed temperature or let the system automatically adjust based on the ambient environment, providing the ultimate flexibility for varying workshop conditions.

Multi-Level Safety Protection
Safety is integrated into every component. The chiller includes flow protection alarms, compressor over-current protection, and high/low-temperature alerts. These features ensure that both the chiller and your expensive laser source are protected from unexpected failures.
商品詳細
- Barbed Brass Connectors: Ensures leak-proof water connection.
- Visual Water Level Gauge: Easy monitoring of tank capacity.
- Universal Wheels: High-mobility for flexible factory layout.
- Dust-Proof Filter: Easily removable for routine cleaning.
オプション品
- Customizable Inlet/Outlet sizes.
- Heater options for cold climate operation.
- Dual water inlet/outlet configuration.
Technical Operations
Ventilation Distance: To ensure the heat exchange efficiency of the condenser, keep the air outlet (back) at least 1.5 meters away from obstacles. Side air inlets must maintain a clearance of at least 0.5 meters to allow sufficient airflow.
Working Principle: The unit operates via a closed-loop refrigeration cycle. The compressor pressurizes the refrigerant, which absorbs heat from the circulating water through the evaporator and releases it via the air-cooled condenser, maintaining a precise ±0.3℃ environment.
FAQ
Q: What type of water should be used?
A: Purified water or distilled water is highly recommended to prevent mineral scaling in the laser tube. You can find more maintenance tips at Chiller Industrial.
Q: Does it comply with international safety regulations?
A: Yes, our design follows the ISO Standard for industrial refrigeration safety and performance.
Q: Why is the “Room Temp Over-high Alarm” ringing?
A: This occurs when the ambient temperature exceeds 45°C. Ensure the workshop is well-ventilated to help the chiller dissipate heat effectively.