CW-5300 Industrial Water Chiller
2.1kW Cooling
Laser & Industrial
製品紹介
The CW-5300 Industrial Chiller is designed for reliable and powerful cooling of laser and industrial equipment. Featuring advanced temperature control, easy operation, and a compact design, it’s perfect for maintaining optimal performance in demanding environments. Sturdy handles provide easy portability, while the durable construction ensures long-lasting service.
製品仕様
| Specifications | Parameter Value |
|---|---|
| モデル | CW-5300 |
| Voltage Options | AC 220-240V (50/60Hz) / AC 110V (60Hz) |
| 冷却能力 | 2.1KW / 7165Btu/h / 2210Kcal/h |
| 温度安定性 | ±0.3℃ |
| Pump Specifications | Power: 88W | Max Head: 25M | Max Flow: 25L/min |
| タンク容量 | 6 Liters |
| Dimensions | 540 × 350 × 660 mm (L×W×H) |
製品の特徴

Advanced Temperature Management
The CW-5300 offers ultra-precise temperature control with ±0.3°C stability. It features two specialized control modes: Constant mode for fixed cooling and Intelligent mode which adjusts automatically to the ambient temperature, preventing water condensation on expensive equipment.

Rugged and Portable Design
Built with durability in mind, this chiller features a compact footprint and sturdy top-mounted handles for easy mobility around the workspace. The sheet metal casing is treated for rust resistance, ensuring a long-lasting service life in tough industrial conditions.
Product Details & Optional Items
The unit incorporates a high-performance compressor and a large-flow pump to ensure efficient heat exchange.
- Refrigerant Compatibility: Supports R410a or R407C, meeting various environmental standards.
- Inlet/Outlet: Standard OD 10mm barbed connectors for quick and secure hose connections.
- Portability: Integrated heavy-duty handles for safe lifting and transport.
- Safety Alarms: Includes water flow protection, high/low temperature alarms, and compressor overload protection.
通気距離
To maintain peak cooling efficiency (2.1kW), adequate airflow is essential. Please observe the following spacing requirements:
- Back Side (Air Outlet): Maintain a distance of at least 50cm from walls or other equipment.
- Side Vents (Air Inlets): Ensure at least 30cm of clearance on both sides for optimal intake.
製品の動作原理
The CW-5300 utilizes a standard vapor-compression cycle. Distilled water is chilled in the internal tank and pumped through the external equipment, absorbing waste heat. This warm water returns to the chiller’s evaporator, where the refrigerant absorbs the heat. The compressor then transfers this energy to the condenser, where high-velocity fans dissipate the heat into the atmosphere, allowing the chilled water to recirculate continuously.