HLFL-2000 Fiber Laser Chiller
7KW Cooling
3HP Power
The HLFL-2000 utilizes a high-lift 42m pump. Always ensure the water loop is fully primed and air-purged before the first start-up to prevent cavitation and protect the 480W pump motor.
Product Introduction
The HLFL-2000 Fiber Laser Chiller provides robust and reliable cooling performance for high-power lasers, CNC machine tools, and other demanding industrial equipment. Designed for high performance and extreme durability, this chiller features advanced dual-temperature control circuits that independently manage the laser source and the optical components. Its robust construction and 18-liter tank capacity ensure consistently high cooling efficiency, making it ideal for large-scale factories, workshops, and intensive manufacturing environments where 24/7 uptime is critical.
Product Parameters
| Parameter | Specification |
|---|---|
| Model | HLFL-2000 (3000 Series Platform) |
| Voltage / Frequency | AC 220-240V / 50Hz |
| Compressor Power | 4100W |
| Cooling Capacity | 3HP / 7KW ±5% |
| Temperature Stability | ±0.5℃ (Dual Temp Control) |
| Electric Heating Power | 400W + 1800W (Dual System) |
| Pump Lift / Flow | Max Lift: 42m | Rated Flow: 70L/min |
| Tank Capacity | 18 Liters |
| Water Outlets | Chilled & Normal Temp φ10 Quick Connectors |
| Dimensions | 740 × 550 × 960 mm (L×W×H) |
Product Features

Dual Cooling System for Fiber Lasers
The HLFL-2000 features an intelligent dual-path cooling design. This allows the system to simultaneously provide chilled water for the laser source and normal-temperature water for the optical lens. This synchronized cooling significantly reduces condensation risks and extends the lifespan of sensitive fiber laser components.

Advanced Safety & Diagnostics
Safety is integrated into the core electronics, featuring dual flow alarms, high/low temperature alerts, and compressor overload protection. Following international **[ISO Standard](https://www.iso.org/standard/72393.html)** safety protocols, the HLFL-2000 also includes sensor failure diagnostics to prevent hardware damage before it occurs.
Product Details
- Refrigerant: Optimized for R410a/R22 high-efficiency heat exchange.
- Construction: Heavy-duty steel frame with industrial-grade casters.
- Quick Connectors: Dual φ10 connectors for rapid deployment.
- Pump: Powerful 480W motor capable of a 42m max head.
Optional Items
- Customized voltage configurations (3-Phase 380V available).
- Enhanced heater kits for sub-zero climate operation.
- Remote monitoring and alarm output communication ports.
- Customizable plumbing sizes for specific CNC interfaces.
Technical Operation
Ventilation Distance: To maintain the rated 7KW cooling capacity, ensure the chiller’s air outlet is at least 1.5 meters away from obstacles. Side air inlets require a clearance of at least 0.5 meters to ensure sufficient airflow for the high-power condenser.
Product Working Principle: The HLFL-2000 utilizes a closed-loop refrigeration cycle. The compressor drives refrigerant through an evaporator where it absorbs heat from the circulating water. The dual-path system then distributes the cooled water at two different temperature setpoints, while heat is dissipated through the forced-air condenser.
FAQ
Q: Is the HLFL-2000 suitable for 3000W lasers?
A: While based on the 3000 series platform, it is optimized for 2000W-3000W fiber lasers. For higher loads, please check our full catalog at **[Chiller Industrial](https://chillerbath.com/)**.
Q: Why does it have two heating powers (400W + 1800W)?
A: The dual system allows for independent temperature stabilization in cold environments, ensuring both the laser head and laser source reach operating temperature quickly.
Q: What maintenance is required?